• New air-flap outlet technology for high airflow
  • Easy mounting
  • Protection type/Environmental ratings by independent testing agencies
  • Two optional systems for optimal airflow (FPI/FPO)
  • Industry-common enclosure cut-out sizes
  • Single filter mat system design


  • Filter fans are used to provide "cooling" by forced air-circulation in enclosures and cabinets containing eletrical/ electronic and other components. The interior temperature of an enclosure can be reduced by channelling cooler, filteredmore
    Unit of Measure

    Specifications

    Operating Voltage

    DC 24 V

    Air Volume, Free Blowing

    104.8 cfm (178 m3/h)

    Air Volume with Exhaust Filter

    91.8 cfm (156 m3/h)

    Current Consumption

    500 mA

    Power Consumption

    12.0 W

    Average Noise Level (DIN EN ISO 4871)

    63 dB (A)

    Mounting Depth

    4.6 inches (117 mm)

    Weight (approx.)

    3.3 lbs. (1.5 kg)

    Filter mat

    G3

    Technical Data

    Axial Fan, Ball Bearing

    service life L10 at +104 °F (+40 °C): min. 80,000 h
    fan body aluminum, plastic impeller

    Connection

    3-pole clamp for AWG 14 (2.5 mm2), clamping torque 0.8 Nm max.

    Housing, Hood, Flaps

    plastic UL 94V-0, light grey;
    UV light resistant according to UL 746C (f1)

    Enclosure Cut-Out

    6.93 x 6.93+0.04 inches (176 x 176+1 mm)
    Mounting Frame1 4 built-in ratchet push levers for mounting (6 ratchet stops to accommodate for wall thicknesses Gauge 9 to 19 or 1 – 4 mm). Additional screw mounting possible if needed.

    Filter Mat

    G3 acc. to DIN EN 779, average arrestance Aa 84 %

    Filter Material

    synthetic mesh with progressive construction, temperature resistant to +212 °F (+100 °C), self-extinguishing class F1, moisture resistant to 100 % RH, reusable

    Operating Temperature

    -13 to +158 °F (-25 to +70 °C)

    Storage Temperature

    -40 to +158 °F (-40 to +70 °C)

    Operating/Storage Humidity

    Max. 90 % RH (non-condensing)

    Protection Type/Protection Class

    IP54 / I (grounded)

    Environmental Rating UL/NEMA

    UL TYPE 12 / NEMA 12

    Approvals

    VDE, EAC, UL submitted

    Note

    other voltages on request
    • 1 Drilling hole markings for screw mounting are indicated on mounting frame.