Unit of Measure

Specifications

Voltage

230 VAC

Scale / Range

-20 to 60 ºC

Contact Type

SPDT / Change-over

Max. Inrush Current

AC 16 A for 10 sec.
Agency Approvals1 CSA-US, VDE

Technical Data

Switching Difference

7 ºF (4 K) ± 1.8 ºF (1 K) Tolerance
at 68 ºF (20 ºC)

Sensor Element

NTC

Reaction Time

approx. 5 sec

Service LIfe

> 50,000 cycles

Max. Switching Capacity (Relay Output)

8 A resistive / 1.6 A inductive at 120 VAC
8 A resistive / 1.6 A inductive at 240 VAC
4 A at 24 VDC

Connection

5-pole terminal, clamping torque 0.5Nm max.: solid wire - AWG 14 max. (2.5mm2) stranded wire (with wire end ferrule) - AWG 16 max. (1.5mm2)

Housing

Plastic, UL 94V-0, light gray

Mounting

Clip for 35 mm DIN rail (EN 60 715)

Mounting Position

Vertical

Operating Temperature

-22 to 140 ºF (-30 to 60 ºC)

Storage Temperature

-40 to 185 ºF (-40 to 85 ºC)

Dimensions

2.54 x 1.65 x 1.5 inches (64.5 x 42 x 38 mm)

Weight

Approx. 2.5 oz (70 g)

Protection Type

IP20
  • 1 CSA-US tested according to UL Standard No. 873