Unit of Measure
Specifications
Voltage |
N/A DC 12-48 V (min. DC 10 V, max. DC 60 V) |
Setting Range |
N/A 40 to 90 %RH |
Agency Approvals |
N/A VDE submitted |
Technical Data
Contact Type |
N/A SPDT / change-over contact (relay) |
Service LIfe |
N/A >100,000 cycles (at 10 mW) |
Max. Switching Capacity (Relay Output) |
N/A 0.5 A at DC 48 V |
Operating/Storage Humidity |
N/A Max. 95 %RH (non-condensing) |
Connection1 | N/A 5-pole terminal, clamping torque 0.5 Nm max.: solid/stranded wire - AWG 14 max. (2.5 mm2) |
Housing |
N/A Plastic, UL 94V-0, light grey |
Mounting |
N/A Clip for 35 mm DIN rail, EN 60715 |
Mounting Position |
N/A Vertical |
Dimensions |
N/A 2.54 x 1.65 x 1.5" (64.5 x 42 x 38 mm) |
Weight |
N/A Approx. 2.5 oz. (70 g) |
Protection Type |
N/A IP20 |
Reaction Time |
N/A Approx. 5 sec. |
Optical Indicator |
N/A LED |
Switching Difference (temperature) |
N/A 5 %RH (± 3 %RH tolerance) at +77 °F (+25 °C) and 50 %RH |
Switching Load |
N/A DC 10 mW (at 0.1 V, 100 mA or 1 mA, 10 V) |
Operating/Storage Temperature |
N/A +32 to +140 °F (0 to +60 °C) / -4 to +158 °F (-20 to +70 °C) |
- 1 When connecting with stranded wires, wire end ferrules must be used.