Unit of Measure
                    
               
        
            Specifications
| Model1 | N/A Thermostat with internal sensor | 
| Power | N/A 200 W | 
| Voltage | N/A DC 24 V | 
| Setting Range2 | N/A -4 to 104 °F | 
Technical Data
| Rec. pre-fuse T (time-delay) | N/A 25.0 A | 
| Heating Element | N/A High performance cartridge heater | 
| Overheat Protection | N/A With automatic reset and second-tier one shot fuse to protect against overheating in case of fan failure | 
| Heat Sink | N/A Extruded aluminum profile | 
| Wiring Compartment | N/A Plastic, UL 94V-0, black | 
| Axial Fan, Ball Bearing | N/A 50,000 h at 77 ºF (25 ºC) | 
| Air Flow, Free Blowing | N/A 94 cfm (160 m3/h) | 
| Connection3 | N/A 2-pole „Push-In“ connection clamp stranded wire AWG 16 (1.5 mm2) with strain relief; max. AWG 12 (2.5 mm2) | 
| Mounting | N/A M5 screws and washers (not included), torque 2 Nm max. | 
| Position | N/A Vertical airflow (air outlet up) | 
| Dimensions | N/A 3.9 x 5.7 x 6.5" (100 x 145 x 166 mm) | 
| Weight | N/A 2.86 lbs. (1.3 kg) | 
| Operating Temperature | N/A -4 to +167 °F (-20 to +75 °C) | 
| Storage Temperature | N/A -40 to +176 °F (-40 to +80 °C) | 
| Operating/Storage Humidity | N/A max. 90 % RH (non-condensing) | 
| Protection Type | N/A IP20 | 
| Protection Class | N/A II (double insulated) | 
| Approvals | N/A UL File No. E234324, VDE, EAC | 
- 1 The external sensor needs to be ordered separately.
- 2 Switching difference temperature: 3 K (±1 K tolerance) at +77 °F (+25 °C), 50 % RH; Switching difference humidity: 4 % RH (±1 % tolerance) at +77 °F (+25 °C), 50 % RH.
- 3 When connecting with stranded wires, wire end ferrules must be used.