Unit of Measure

Specifications

Operating Voltage 

N/A 100-240 VAC

Temperature Setting Range

N/A 32 to 140 ºF

Humidity Setting Range

N/A 50 to 90 % RH

Technical Data

Switching Difference (Temperature)

N/A K (±1 K tolerance) at 25 ºC (77 ºF)

Switching Difference (Humidity)

N/A 4 % RH (± 1 % tolerance) at 25 ºC (77 ºF)

Reaction Time (Humidity)

N/A approx. 5 sec.

Contact Type

N/A change-over contact (relay)

Service LIfe

N/A VDE: NO/NC > 15,000 cycles, UL: NO/NC > 30,000 cycles
Max. Switching Capacity (Relay Output)1 N/A 10 A resistive / 1.6 A inductive at AC 240 V, 0.6 A at DC 60 V

Max. Inrush Current

N/A AC 30 A for 10 sec.
Connection2 N/A 5-pole terminal, clamping torque 0.5 Nm max: solid/stranded wire AWG 14 max. (2.5 mm²)

Housing

N/A Plastic, UL 94V-0, light grey

Mounting

N/A Clip for 35 mm DIN rail, EN 60715

Mounting Position

N/A vertical

Operating/Storage Temperature

N/A -40 to 140 ºF (-40 to 60 ºC)

Operating/Storage Humidity

N/A max. 95 % RH (non-condensing)

Dimensions (H x W x D)

N/A 3.0 x 2.4 x 1.7 inches (77 x 60 x 43 mm)

Weight

N/A approx. 3.5 oz (100 g)

Protection Type

N/A IP20

Agency Approvals

N/A UL File No. E164102, VDE, GOST-R
  • 1 Not UL confirmed
  • 2 When connecting with stranded wires, wire end ferrules must be used.