Unit of Measure
Specifications
Voltage |
N/A 230 VAC |
Scale / Range |
N/A 0 to 60 ºC 50 to 90% RH |
Contact Type |
N/A SPDT / Change-over |
Agency Approvals |
N/A UL, VDE |
Technical Data
Switching Difference (Hysteresis) |
N/A
Approx. 3.6 ºF (2 K) ± 1 K tolerance approximately 4% RH ± 1% tolerance |
Response Time |
N/A Approx. 5 sec |
Relay Output (Switching Capacity) |
N/A
NC: AC 240 V - 6 A resistive, 1 A inductive NO: AC 240 V - 8 A resistive, 1.6 A inductive NC: AC 120 V - 6 A resistive, 1 A inductive NO: AC 120 V - 8 A resistive, 1.6 A inductive DC 24 V - 4 A resistive |
Service LIfe |
N/A > 100,000 cycles |
Function Control Light |
N/A LED |
Connection |
N/A 5-pole terminal for AWG 14 max. (2.5 mm²) |
Mounting |
N/A Clip for 35 mm DIN rail (EN 60 715) |
Dimensions (H x W x D) |
N/A 3.03 x 2.36 x 1.69 inches (77 x 60 x 43 mm) |
Housing |
N/A Plastic, UL 94V-0, light gray |
Weight |
N/A 6 oz (170 g) |
Mounting Position |
N/A Vertical |
Operating Temperature |
N/A 32 to 140 ºF (0 to 60 ºC) |
Storage Temperature |
N/A -4 to 176 ºF (-20 to 80 ºC) |
Protection Type |
N/A IP20 |