Unit of Measure
Specifications
Free Blowing Air Flow (with Filter Mat) |
N/A 294 cfm (500 m³/h) |
Voltage |
N/A 230 VAC |
Environmental Ratings |
N/A IP32 |
Agency Approvals |
N/A UL intended, VDE (230V only) |
Technical Data
Air Flow Free Blowing (without Filter Mat) |
N/A 383 cfm (650 m³/h) |
Power Consumption |
N/A 64 W |
Enclosure Cut-Out |
N/A 9.8 x 9.8 inches (250 x 250 + 0.4 mm) |
Mounting Depth |
N/A 4.2 inches (107 mm) |
Weight |
N/A 5.7 lbs (2.6 kg) |
Housing |
N/A Plastic, UL 94V-0, light gray, weather proof and UV light resistant according to UL 746C (f1) |
Filter Mat |
N/A Coarse grade, filtering degree 85 %, G3 (DIN EN 779) |
Filter Material |
N/A Synthetic fiber with progressive construction, temperature resistant to 212 ºF, self-extinguishing class F1. Moisture resistant to 100% RH. Can be cleaned by washing or vacuuming for reuse. Replacement filter mats available on request. |
Axial Fan, Ball Bearing |
N/A Aluminum frame, plastic impeller UL 94V-0, Operational life min. 50,000 h at 77 ºF (RH 65 %). Operating temperature -49 ºF to 158 ºF 2 lead wires 4" long with pressure clamps, type AWG 14 max. |
Connection |
N/A 3-pole clamp AWG 14 max. (2.5 mm²) |
Operating Temperature |
N/A -13 to 158 ºF (-25 to 70 ºC) |
Storage Temperature |
N/A -13 to 158 ºF (-25 to 70 ºC) |
Protection Type |
N/A IP32 |
Protection Class |
N/A I (grounded) |