• Very low noise
  • Minimal mounting depth
  • High air volume
  • High reliability
  • Time-saving installation and mat exchange
Roof filter fans and roof exhaust filters are used in enclosures from which warm air must be diverted due to increased heat development. The ready-to-connect and low-noise roof filter fan is used to expel warm air from within the enclosure. Alternatively, the roof exhaust filter provides passive ventilation. The RFP 018 series comes in two versions: one utilizes four small axial fans, improving reliability and maintaining continuous operations even if one of the fans should fail; the second uses a larger single high capacity fan.
Unit of Measure

Technical Data

Axial fans, ball bearing

N/A service life min. 50,000 h at 77 °F (25 °C) and 65 %RH
aluminum fan body, plastic rotor

Connection

N/A 3-pole clamp, AWG 14 (2.5 mm²), clamping torque 0.8 Nm max.

Housing

N/A plastic, UL 94V-0, light grey;
UV light resistant according to UL 746C (f1)

Filter mat

N/A G3 (1 packing unit = 3 pcs.)

Filter material

N/A synthetic fiber with progressive construction, temperature resistant to 212 °F, self-extinguishing class F1; moisture resistant to 100 %RH, reusable - can be cleaned by washing or vacuuming

Operating / Storage humidity

N/A max. 90 % RH (non-condensing)

Protection class / Protection type

N/A I (grounded) / IP32

Approvals

N/A GOST TR (all), VDE (AC 230 V only); UL intended

Important note

N/A For reasons of pressure compensation, the roof filter fan must always be operated in combination with another filter fan (e.g. Part No. 01803.0-00) or a passive intake filter (e.g. Part No. 11803.0-00).