Unit of Measure

Specifications

Model1 N/A Thermostat with internal sensor

Power

N/A 800 W

Voltage

N/A DC 24 V
Setting Range2 N/A -4 to 104 °F

Technical Data

Rec. pre-fuse T (time-delay)

N/A 25.0 A

Heating Element

N/A High performance cartridge heater

Overheat Protection

N/A With automatic reset and second-tier one shot fuse to protect against overheating in case of fan failure

Heat Sink

N/A Extruded aluminum profile

Wiring Compartment

N/A Plastic, UL 94V-0, black

Axial Fan, Ball Bearing

N/A 50,000 h at 77 ºF (25 ºC)

Air Flow, Free Blowing 

N/A 94 cfm (160 m3/h)
Connection3 N/A 2-pole „Push-In“ connection clamp stranded wire AWG 16 (1.5 mm2) with strain relief; max. AWG 12 (2.5 mm2)

Mounting

N/A M5 screws and washers (not included), torque 2 Nm max.

Position

N/A Vertical airflow (air outlet up)

Dimensions

N/A 3.9 x 5.7 x 6.5" (100 x 145 x 166 mm)

Weight

N/A 2.86 lbs. (1.3 kg)

Operating Temperature

N/A -4 to +167 °F (-20 to +75 °C)

Storage Temperature

N/A -40 to +176 °F (-40 to +80 °C)

Operating/Storage Humidity

N/A max. 90 % RH (non-condensing)

Protection Type

N/A IP20

Protection Class

N/A II (double insulated)

Approvals

N/A UL File No. E234324, VDE, EAC
  • 1 The external sensor needs to be ordered separately.
  • 2 Switching difference temperature: 3 K (±1 K tolerance) at +77 °F (+25 °C), 50 % RH; Switching difference humidity: 4 % RH (±1 % tolerance) at +77 °F (+25 °C), 50 % RH.
  • 3 When connecting with stranded wires, wire end ferrules must be used.