Unit of Measure

Specifications

Operating Voltage

AC 230 V, 50/60 Hz

Heating Capacity

500 W

Pre-Fuse T (Time-Delay)

4 A

Technical Data

Heating Element

High performance cartridge

Temperature Safety Cut-Out

With automatic reset and second-tier one shot fuse

Axial Fan, Ball Bearing

50,000 h at 77 ºF (25 ºC)

Air Flow, Free Blowing 

88 cfm (150 m³/h)

Connection

2-pole dual pressure clamp for solid, AWG 14 max (2.5 mm²) stranded wire (with wire end ferrule) AWG 16 max. (1.5 mm²)

Housing

plastic, UL 94V-0, black

Mounting

M6 screws and washers (not included), torque 2 Nm max.

Mounting Position

Vertical airflow (air outlet up)

Operating Temperature

UL: 14 to 104 ºF (-10 to 40 ºC) VDE: 14 to 122 ºF (-10 to 50 ºC)

Storage Temperature

-49 to 158 ºF (-45 to 70 ºC)

Dimensions (H x W x D)

6.65 x 5.0 x 3.5 inches (169 x 127 x 89 mm)

Weight

approx. 3.1 lb (1.4 kg)

Protection Type

IP20

Protection Class

heater: II (double insulated), fan: I (grounded)

Agency Approvals

VDE, UL File No. E234324, GOST-R

Important Note

Important Note

Other heating capacities and voltages available on request.

Heater may only be operated together with fan (min. 88 cfm).
Danger of overheating!