Unit of Measure

Specifications

Operating Voltage

N/A AC 230 V, 50/60 Hz

Heating Capacity

N/A 600 W

Pre-Fuse T (Time-Delay)

N/A 4 A

Technical Data

Heating Element

N/A High performance cartridge

Temperature Safety Cut-Out

N/A With automatic reset and second-tier one shot fuse

Axial Fan, Ball Bearing

N/A 50,000 h at 77 ºF (25 ºC)

Air Flow, Free Blowing 

N/A 88 cfm (150 m³/h)

Connection

N/A 2-pole dual pressure clamp for solid, AWG 14 max (2.5 mm²) stranded wire (with wire end ferrule) AWG 16 max. (1.5 mm²)

Housing

N/A plastic, UL 94V-0, black

Mounting

N/A twist clip for 35 mm DIN rail, EN 60715

Mounting Position

N/A Vertical airflow (air outlet up)

Operating Temperature

N/A UL: 14 to 104 ºF (-10 to 40 ºC) VDE: 14 to 122 ºF (-10 to 50 ºC)

Storage Temperature

N/A -49 to 158 ºF (-45 to 70 ºC)

Dimensions (H x W x D)

N/A 6.65 x 5.0 x 3.5 inches (169 x 127 x 89 mm)

Weight

N/A approx. 3.1 lb (1.4 kg)

Protection Type

N/A IP20

Protection Class

N/A heater: II (double insulated), fan: I (grounded)

Agency Approvals

N/A VDE, UL File No. E234324, GOST-R

Important Note

Important Note

N/A Other heating capacities and voltages available on request.

Heater may only be operated together with fan (min. 88 cfm).
Danger of overheating!