Unit of Measure

Specifications

Operating Voltage

N/A 230 VAC, 50/60Hz

Scale / Range

N/A 40 to 90 % RH

Contact Type

N/A SPDT / Change-over
Agency Approvals1 N/A CSA-US, VDE

Technical Data

Switching Difference

N/A 5 % RH (± 1 % tolerance) - at 77 ºF (25 ºC) and 50 % RH

Service LIfe

N/A > 50,000 cycles

Relay Output Max. Switching Capacity

N/A 8A resistive / 1.6 A inductive at 120 VAC
8 A resistive / 1.6 A inductive at 240 VAC
4A at 24 VDC

Connection

N/A 5-pole terminal, clamping torque 0.5Nm max.:
    solid wire - AWG 14 max. (2.5mm2)
    stranded wire (with wire end ferrule) - AWG 16 max. (1.5mm2)

Mounting

N/A Clip for 35 mm DIN rail (EN 60 715)

Dimensions

N/A 2.54 x 1.65 x 1.5 inches (64.5 x 42 x 38 mm)

Housing

N/A Plastic, UL 94V-0, light gray

Operating Temperature

N/A 32 to 140 ºF (0 to 60 ºC)

Storage Temperature

N/A -4 to 176 ºF (-20 to 80 ºC)

Protection Type

N/A IP20

Reaction Time

N/A approx. 5 sec

Max. Inrush Current

N/A AC 16 A for 10 sec

Mounting Position

N/A Vertical

Max. Storage Humidity

N/A 90 % RH (non-condensing)

Weight (Approx.)

N/A 2.3 oz (65 g)
  • 1 CSA-US tested according to UL Standard No. 873