Unit of Measure

Specifications

Free Blowing Air Flow

37 cfm (63 m³/h)

Voltage

120 VAC
Environmental Ratings1 UL Type 1 / IP55

Agency Approvals

UL

Technical Data

Version

Standard

Air Flow with Exit Filter 

28 cfm (48 m³/h)

Power Consumption

15 W

Current Consumption

180 mA

Average Noise Level at 3 ft (DIN EN ISO 4871)

40 dB (A)

Grill Size

6 x 6 inch

Enclosure Cut-Out

4.9 x 4.9 inches (125 x 125 + 0.4 mm)

Mounting Depth 

2.3 inches (58 mm)

Weight

2.2 lb (1 kg)

Filter Fan Housing

Plastic, UL 94V-0, light gray

Filter Fan Hood

Plastic, UL 94V-0, light gray, weather proof and UV light resistant according to UL 746C (f1)

Mounting Frame

With double sided industrial adhesive band for affixing to the outside of enclosure. Certain operating circumstances may make the additional use of screws necessary.

Filter Mat

Medium grade 350 g/m2, filtering degree 94 % for particle Ø < 10 µm, G4 (EN 779)

Filter Material

Synthetic fiber with progressive construction, temperature resistant to 212 ºF, self-extinguishing class F1. Moisture resistant to 100% RH. Can be cleaned by washing or vacuuming for reuse. Replacement filter mats available on request.

Axial Fan, Ball Bearing

Aluminum frame, plastic impeller UL 94V-0, Operational life min. 50,000 h at 77 ºF (RH 65 %). Operating temperature -49 ºF to 158 ºF 2 lead wires 4" long with pressure clamps, type AWG 14 max.

Connection

2 wires w/ cage clamps, AWG 14 (2.5 mm²), length 4" (100 mm)

Operating Temperature

14 to 158 ºF (-10 to 70 ºC)

Storage Temperature

-40 to 158 ºF (-40 to 70 ºC)
Protection Type2 IP55 (according to VDE)

Protection Class

I (grounded)
  • 1 Using fine filter mat type F5 increases the protection type to UL Type 12 but reduces the air volume
  • 2 Using fine filter mat type F5 increases the protection type to UL Type 12 but reduces the air volume