Unit of Measure

Specifications

Free Blowing Air Flow

N/A 324 cfm (550 m³/h)

Voltage

N/A 24 VDC
Environmental Ratings1 N/A UL Type 1 / IP55

Agency Approvals

N/A UL

Technical Data

Version

N/A Standard

Air Flow with Exit Filter 

N/A 177 cfm (300 m³/h)

Grill Size

N/A 11 x 11 inch

Enclosure Cut-Out

N/A 9.8 x 9.8 inches (250 x 250 + 0.4 mm)

Mounting Depth 

N/A 4.2 inches (107 mm)

Weight

N/A 5.9 lb (2.7 kg)

Filter Fan Housing

N/A Plastic, UL 94V-0, light gray

Filter Fan Hood

N/A Plastic, UL 94V-0, light gray, weather proof and UV light resistant according to UL 746C (f1)

Mounting Frame

N/A With double sided industrial adhesive band for affixing to the outside of enclosure. Certain operating circumstances may make the additional use of screws necessary.

Filter Mat

N/A Medium grade 350 g/m2, filtering degree 94 % for particle Ø < 10 µm, G4 (EN 779)

Filter Material

N/A Synthetic fiber with progressive construction, temperature resistant to 212 ºF, self-extinguishing class F1. Moisture resistant to 100% RH. Can be cleaned by washing or vacuuming for reuse. Replacement filter mats available on request.

Axial Fan, Ball Bearing

N/A Aluminum frame, plastic impeller UL 94V-0, Operational life min. 50,000 h at 77 ºF (RH 65 %). Operating temperature -49 ºF to 158 ºF 2 lead wires 4" long with pressure clamps, type AWG 14 max.

Connection

N/A 3-pole terminal AWG 14 max. (2.5 mm²)

Operating Temperature

N/A -13 to 140 ºF (-25 to 60 ºC)

Storage Temperature

N/A -13 to 140 ºF (-25 to 60 ºC)
Protection Type2 N/A IP55 (according to VDE)

Protection Class

N/A I (grounded)
  • 1 Using fine filter mat type F5 increases the protection type to UL Type 12 / IP55 but reduces the air volume
  • 2 Using fine filter mat type F5 increases the protection type to UL Type 12 / IP55 but reduces the air volume